Joint sealing and staggering
Every joint sealed with the specified compound and staggered between layers, because an aligned joint through the full thickness is a direct path from ambient to the cold face.
Cellular glass is chosen because it is closed-cell, load-bearing and does not absorb water. None of that survives bad detailing. The material is rigid and brittle, the substrate contracts underneath it, and every joint is a potential vapour path — so the detail drawings, not the material certificate, decide whether the system works.

Cellular glass fails at the joints and at the supports, not in the block. These are the details that have to be drawn before anything is ordered.
Every joint sealed with the specified compound and staggered between layers, because an aligned joint through the full thickness is a direct path from ambient to the cold face.
The pipe shrinks as it cools and the insulation does not follow it. Contraction joints are located and sized so the movement is absorbed where it is designed to be, not by cracking a block.
Cellular glass carries load, which is why it is used at supports. The bearing area, compressive stress and load spreading are calculated rather than assumed.
Full-thickness vapour stops at intervals and at every termination, so a local barrier failure cannot wet the whole run.
Rapid cooldown puts the hot face and cold face of a block at very different temperatures. Block size, joint width and sealant selection all follow from the cooldown rate, which is why we ask for it before detailing anything.

We start from the service temperature, the cooldown rate and the support arrangement, calculate the contraction over each run and the bearing stress at each support, and then draw the joints, vapour stops and supports as buildable details with dimensions rather than as notes on a specification.
Drawn at the level an installer can build from, because this is a system where interpretation on site is the main failure mode.
Joints, contraction joints, vapour stops, supports and terminations, dimensioned.
Movement by run, joint spacing and width, with the temperature basis stated.
Bearing area and compressive stress at each support against the rated strength.
Block grade, sealant, mastic and finish by service, with temperature limits.
Quantities by detail type, suitable for enquiry and for procurement.
The sequence and workmanship points this system is least tolerant of.

It is the right answer where load-bearing capacity, closed-cell structure and fire behaviour all matter at once. It is the wrong answer where the geometry is complex, the budget is tight or the installer has no experience with it, because its advantages depend entirely on workmanship that other materials forgive.
Industrial Insulation Catalogue
Engineering scope, calculation and documentation services, material families and application capability in a single document.
ERATHERM works as an engineering partner for operators, EPC contractors and equipment manufacturers. Calculation, design, documentation and specification work is delivered remotely under the client's document control procedure; inspection, site supervision and application teams are mobilised to site.
Yes. The block itself is closed-cell and will not absorb water, but the joints between blocks are not. A continuous vapour barrier and full-thickness vapour stops are what stop moisture travelling along the joint network to the cold face.
From the contraction of the substrate over the run, which follows from the temperature range and the pipe material. A default spacing taken from a catalogue will be wrong at both ends of the temperature range, and cracked blocks are the usual evidence.
Because it carries compressive load without creeping, so the pipe shoe can bear directly on insulation instead of on a steel bridge through it. That removes one of the largest heat leak paths in a cold system.
Unsealed or aligned joints. The material tolerates very little improvisation, and a run installed quickly by a crew used to flexible insulation will usually have both problems. This is why we detail it fully and why inspection before cladding matters.
Cellular glass details usually sit alongside the rest of a cold system scope.
Detail design
Cellular glass detail Valve and flange jacket detail Tank bottom cryogenic detail Thermal expansion and supportsWe will calculate the contraction, check the supports and return detail drawings an installer can build from without interpretation.